The RC2105 Series 2000 wireless heating system controller utilizes reliable Spread Spectrum Radio technology. Together with other existing Trs Systems WT2630A wireless space sensors and OST2630 wireless outside air temperature (OSA) sensors, the RC2105 controller will control the boiler system based on the average space temperature (up to 12 zones) and wireless outside air temperature. If the OSA temperature is below OSA set point and the average temperature is lower than the average space temperature set point, the heating system will be activated after a preset time delay (adjustable) by a relay output from the RC2105 controller to the boiler control system. The RC2105 provides maximum flexibility with extensive system adjustability, sensor selectability, alarms and reliable wireless sensor capability.
The RC2105 Series 2000 is also capable of communicating wirelessly with the Trs Systems RM9520 Receiver/Server. This enables the user to control and monitor their buildings remotely through the Local Area Network and/or the Internet.
The maximum radio transmission distance is dependent on building type. The maximum open-air transmission distance is one mile. In a typical commercial building with steel I-beam construction, concrete floors with reinforcing rod, and metal stud walls, it can be expected that transmissions will penetrate vertically through floors and horizontally through 200 to 500 feet of walls, furniture and air. Generally a wireless system will cover at least three floors - one floor above and one floor below the receiver location.
Input Voltage:
24 VAC 60 Hz (+10%/-15%)
Power Consumption:
4 VA Maximum
Dimensions:
9-3/8” x 4-5/8” x 2-3/8”
Operating Conditions:
Temperature 15 to 125 deg F
Humidity 5 to 95% RH non-condensing
Sensor Indicating Ranges:
Outside air sensor, -40 to 160 deg F
Space Temperature, 32 to 104 deg F
Accuracy, +/- 1 deg F
Boiler System Control Output:
Three terminals for heating system enable output
(Common, Manual & Auto) – SPST N.O. o Pilot Duty (1 amp max. at 24VAC)
Low Battery/Lost Transmitter Alarm Output:
Pilot Duty Relay Contact (SPST N.O., 1 amp
max. at 24 VAC)
Low Limit Alarm Output:
Pilot Duty Relay Contact (SPST N.O., 1 amp max. at 24 VAC)
Set Point Adjustment Range:
35 to 95 deg F
Case:
NEMA4 Enclosure (Light Gray)
Transparent Cover
UL94V-2 Flammability Rating
RF Characteristics:
Operating Frequency Channel 923.58 MHz o Receiver Sensitivity (avg. power)
–107 dBm o Jam Resistance
60 dB out-of-band rejection
Approvals:
FCC part 15.247
Field Adjustable parameters:
Space temperature set point
Space set point differential
Outside air temperature set point
OA temperature set point differential
Day/night setpoints & schedule
Time of day
Output time delay
Sensor high/low limit range (excludes a particular sensor from the average temperature calculation if its temperature is beyond the
set point limit range)
LED display:
Average space temperature
Space temperatures included in the average calculation
Space temperature set point & differential
Night mode set point offset
Time of day & day/night schedule
Outside air temperature
Outside air set point & differential
Individual space temperature(s)
Low Battery, Lost Sensor & Space Temperature Low Limit Alarms
Sensor limit range for calculation